Enter voltage, current, cable length and cross-section to get the voltage drop in volts and percent and the smallest standard cross-section that meets your limit.
Resistance from the resistivity of copper (0.017241 Ω·mm²/m) or aluminium (0.028264 Ω·mm²/m) at 20 °C, corrected to the conductor temperature. Three-phase: ΔU = √3 · L · I · (R' cos φ + X' sin φ); single-phase and DC use the factor 2.
This is a verification aid: it does not check current-carrying capacity, protection or short-circuit withstand (IEC 60364-5-52, cable maker's data). The engineer signs off.